TestPro Technical Bulletin Multi-Mode Fiber Adapter: 850nm Encircled Flux LED Source

CategoriesMulti-Mode Fiber Adapter

ANSI/TIA-568.3-D Standard specifies the Transmission Performance and Test Requirements for Optical Fiber Cabling. Tier 1 testing of installed optical fiber cabling requires measurements of Attenuation (Optical Loss), Length & Polarity.

For MultiMode Cabling, attenuation measurements are to be taken according to ANSI/TIA-526-14-C. ANSI/TIA-526-14-C specifies that the output of the launch cord must meet requirementsof the specified encircled flux (EF) template. Compliance to EF launch condition ensuresmeasurement repeatability. Below is an example of EF Template indicates target, limiting andoverfilled launch values.

EF Requirements for 50um Fiber at 850nm are defined as limiting values for a set of particular radial values as shown in table below.

TestPro’s Multi-Mode Fiber Adapters use 850nm & 1300nm Dual Wavelength LED Light Source that meet Encircled Flux requirements. The MPX Explorer test instrument from Arden Photonics has been used to verify that Encircled Flux measurements meet the required EF limits. Measurements have been done at end of FC to LC Reference Cord.

Encircled Flux Uncertainty

For field test equipment, a single optical port launces two wavelengths. This will not allow alignment for both wavelength simultaneously. The use of common Mandrel / Mode conditioner for both wavelengths will reduce the margin for compliance within the templates and add uncertainty.

Due to the effects of variation in source wavelengths, mode controller, temperature changes, other physical variations and the measurement equipment, launch conditions at the time of factory calibration will not be identical in the field should any variables change. The use of attenuation artifacts described in IEC 61280-4-1 can help ensure that the equipment produces a launch condition that performs acceptably.